""
solarpvinverter.comPV inverters, 1-500 kW

Guide

How a solar PV inverter works, stage by stage

A PV inverter is an MPPT tracker, a switching converter and a safety device in one box. Here is what happens between the string and the socket — and which parts decide whether the machine lasts ten years.

An inverter does three things at once, and only one of them is "conversion". It tracks the array's maximum power point, it converts DC to a clean 50 or 60 Hz sine wave, and it disconnects instantly when the grid disappears. The block diagram below is the whole machine.

DC inputstrings + SPD DC switch EMIfilter MPPT boostSiC, 20-60 kHz tracking 99.9 % DC bus400 V + caps H-bridgeIGBT / MOSFET Filter + relayLCL, ENS AC out DSP control loop Every stage adds loss: budget 0.4 % in the filter, 1 % in the bridge, 0.3 % in the boost, 0.2 % in wiring.
Power stage of a transformerless string inverter. The DSP loop closes around the DC bus and the AC current.

Maximum power point tracking

A PV cell is a current source in parallel with a diode: its output depends entirely on the load it sees. Sweep the operating voltage and power rises to a single peak, then collapses. The MPPT is a DC-DC converter that continuously nudges the operating point toward that peak — a hill-climbing algorithm running thousands of times a second, at 99.9 % tracking accuracy on our units.

Why it matters in money: a fixed-voltage system loses 10-25 % of the array's energy over a year. The loss is worst in exactly the conditions buyers care about — cold mornings, thin cloud, and hot afternoons when the peak shifts sharply.

Why two MPPTs beat one

Every string on a tracker shares one operating voltage. Put an east-facing string and a west-facing string on the same tracker and the machine finds a compromise that suits neither. Two independent trackers recover 4-8 % of annual yield on a typical complex roof — more than the price difference between a one- and two-MPPT unit.

Protection: what actually fails in the field

  • Surge — lightning on overhead LV networks. Type II SPD on both DC and AC sides is standard on our three-phase range, optional on single-phase.
  • DC arc — a loose MC4 or a rodent-damaged cable. AFCI to IEC 63027 detects the signature and shuts the input down.
  • Islanding — the inverter must not energise a dead line while a lineman works on it. Passive plus active detection to IEC 62116.
  • Heat — the real killer. A unit rated 10 kW at 25 °C that derates to 7 kW at 50 °C is honest; one that claims full power at 60 °C is not.

Communication and monitoring

Wi-Fi for the phone app, RS485/Modbus for a site logger, and dry contacts for a generator or alarm. We do not require a cloud account to commission a unit: local AP mode works offline, which matters on sites where the WiFi password changes with the tenant.

Grid codes, in one table

MarketStandardWhat the inverter must do
EuropeEN 50549-1/-2, VDE-AR-N 4105Frequency/watt and volt/watt response, export limiting
UKG98 / G99Type-tested, G99 fast-track for <16 A per phase
North AmericaUL 1741 SB, IEEE 1547-2018Smart inverter functions, rapid shutdown
AustraliaAS/NZS 4777.2Demand response modes, 50 Hz ride-through
South AfricaNRS 097-2-1Anti-islanding, power quality limits
BrazilABNT NBR 16149 / 16150THD limits, anti-islanding, Portuguese labelling
IndiaIS 16221, CEA regulationsLVRT, reactive power capability

Tell us what you are building

Send the specification and we reply with a sized quotation in one working day.